NJBK10 Motor Protection Relay
NJBK10 series motor protection relay (hereinafter referred to as the protector) suitable for AC 50Hz, rated insulation voltage up to 690V and under, rated working current 1A-200A long-term or intermittent AC motor work overload, open-phase, three-phase imbalance protection.
Product meets IEC60947-4-1 standard requirements
SKU: ELC8777
Categories: Electrical Products, Low Voltage Electric, Protection Relay, Relays
Tags: Low voltage electric, Protective Relay, Replay
Related products
NXB-40 Miniature Circuit Breaker
Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A;
Rated voltage: 240V;
Frequency: 50Hz;
Electromagnetic release type: C, D;
Number of poles: 1P+N;
Mechanical life: 20000 cycles;
Electrical life: 10000 cycles;
Rated short-circuit breaking capacity(Icu): 4500A;
Short-circuit breaking capacity(Ics): 4500A;
Rated impulse withstand voltage(Uimp): 4kV;
CATALOG
NXB-40 Miniature Circuit Breaker PDF
NB1-63 Miniature Circuit Breaker
1.1 Function
protection of circuits against short-circuit currents,protection of circuits against overload currents,switch,isolation.
NB1 circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems.
1.2 Selection
Technical data of the network at the point considered:short-circuit current at the circuit-breaker installation point, which must always be less than the breaking capacity of this device,network normal voltage.
Tripping curves:
B curve (3-5In)
protection for people and big length cables in TN and IT systems.
C curve (5-10In)
protection for resistive and inductive loads with low inrushcurrent.
D curve(10-14In)
protection for circuits which supply loads with high inrush current at the circuit closing
(LV/LV transformers, breakdown lamps).
1.3 Approvals and certificates
Detailed information, please refer to Certificates Table on the last page.
NXB-125G Miniature Circuit Breaker
Rated current: 63, 80, 100(1P, 2P, 3P, 4P), 125(1P, 2P);
Rated voltage: 240V ~ (1P), 415V ~ (2P, 3P, 4P);
Frequency: 50Hz;
Electromagnetic release type: B, C, D;
Number of poles: 1P, 2P, 3P, 4P;
Mechanical life: 20000 cycles;
Electrical life: 6000 cycles (In≤100A); 4000 cycles (In>100A);
Rated short-circuit breaking capacity(Icn): 10000A;
Short-circuit breaking capacity(Ics): 7500A;
Rated impulse withstand voltage(Uimp): 4kV;
CATALOG
NXB-125G Miniature Circuit Breaker PDF
NXB-63H Miniature Circuit Breaker
Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A,;
Rated voltage: 240V ~ (1P, 1P+N), 415V ~ (2 ~ 4P, 3P+N);
Frequency: 50Hz;
Electromagnetic release type: B, C, D;
Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P;
Mechanical life: 20000 cycles;
Electrical life: 10000 cycles;
Rated short-circuit breaking capacity: 10000A;
Short-circuit breaking capacity: 7500A;
Rated impulse withstand voltage: 4kV;
CATALOG
NXB-63H Miniature circuit breaker PDF
DZ158 Moulded Case Circuit Breaker
1.1 Function
protection of circuits against short-circuit currents,protection of circuits against overload currents,switch,isolation.
1.2 Selection
Technical data of the network at the point considered:the earthing systems (TNS, TNC),short-circuit current at the circuit-breaker installation point, which must always be less than the breaking capacity of this device,network normal voltage.
1.3 Approvals and certificates
Detailed information, please refer to Certificates Table on the last page.
CATALOG
DZ158 Moulded Case Circuit Breaker(DC type)
NB3LEU Residual Current Operated Circuit Breaker with Over-current Protection
1.1 Selection
Rated residual operating current
I∆n = 30 mA: additional protection in the case of direct contact.
Tripping class
AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
Tripping curve
B curve (3-5 In) protection and control of the circuits against overloads and short-circuits; protection for people and big
length cables in TN and IT systems.
C curve (5-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current.
1.2 Approvals and certificates
CATALOG
NB3LEU Residual Current Operated Circuit Breaker with Over-current Protection PDF
NBH8 Miniature Circuit Breaker
1.1 Function
protection of circuits against short-circuit currents,protection of circuits against overload currents,switch,isolation.
1.2 Selection
Technical data of the network at the point considered:the earthing systems (TNS, TNC),
short-circuit current at the circuit-breaker installation point, which must always be less than the breaking capacity of this device,network normal voltage.
Tripping curves:
B curve (3-5In)
protection for people and big length cables in TN and IT systems.
C curve (5-10In)
protection for resistive and inductive loads with low inrush current.
1.3 Approvals and certificates
CATALOG
NBH8 Miniature Circuit Breaker PDF